Typus: 3-phase oil immersed distribution transformer
Rated Power: 6300 kVA–180000 kVA
Frequency: 50 Hz / 60 Hz
Normae: IEC 60076 / GB 1094
Customize from Our Standard Product Line
If you spot a near-match in our catalog, we can quickly modify our standard transformers for your application. Adjustments cover capacity, voltage class, cooling type and installation structure.
Build per Your Technical Documents
Send us your specifications or drawings. Our engineering team reviews the design, validates all key parameters with you, and manufactures strictly in accordance with international standards.
Full Custom Design from Concept to Completion
Without formal detailed specs? Share your ideas and functional requirements. We partner with you to develop fully customized transformer solutions, from electrical design and structural layout through to insulation system.
Praecipue adhibetur in regionalibus substationibus nodalibus rete pro transmissione potentiae, conversione voltatis, et distributione. Etiam late adoptatur in connexione gradus-ad-superiora rete, necnon in infrastructuris criticis ut sunt potentia trahens transitus ferroviarii urbani et suppetitia potentiae altius fiduciae pro magnis centris datorum
Transformator oleo-immersus Bardeen 110kV/220kV repraesentat solutionem robustam ingenio confectam pro transmissione potentiae altius voltatis, integratione apparatus substationis, et proiectis depositi energiae renovabilis. Hic transformator oleo-immersus designatus est ad optima postulata fiduciae rete implenda, dum simul stabilitatem operationalem longae durationis et facilitatem manutentionis praebet
The Bardeen 110kV/220kV oil-immersed transformer features an optimized core and coil assembly that reduces no-load losses and improves overall efficiency. The transformer core utilizes high-grade silicon steel with precision stacking techniques to minimize core loss and audible noise, ensuring long-term grid reliability. The winding design employs low-loss copper or aluminum conductors with high mechanical strength to withstand short-circuit forces and thermal cycles. The conservator, breather, and oil-immersion design ensure stable dielectric performance and prolonged insulation life for all high-voltage substation equipment
Bardeen adopts an optimized oil-immersion cooling system that enhances heat dissipation for continuous operation under heavy load conditions. The oil-immersed transformer uses high-quality mineral insulating oil with excellent dielectric properties and thermal conductivity
Transformator oleosus bardeen 110 kV/220 kV optime idoneus est ad integrationem storii energiae renovabilis, connectens activa storii, ut systemata storii energiae batteriarum (BESS) et magnae scale photovoltaicae vel venti agricolae, ad rete transmissionis. Cum storatio energiae renovabilis continue expanditur, instrumenta substationis fidelia critica fiunt ad fluxus electricos bidirectionales, regulandam tensionem, et facultates superandi defectus tractandum, quibus fiducia rete electricum ulterius roboratur
Adaptatio et Flexibilitas Technica
Intellegentes unumquemque proiectum speciales habere specificaciones, bardeen latam adaptationem suae seriei transformatorum oleosorum offert. Societas configurationes adaptatas commutatorum derivationum, optiones aviorum tertiarum, systemata specialia insulationis pro ambientibus asperis, et dispositiones specialis bushing praebet ad constrictiones loci specificas pro proiectis storii energiae renovabilis complendas
| Capacitas accepta - KVA | Tensio Alta – kV | Tensio Baja – V | Symbolus Gruppi Connectionis | Impedantia Ad Cortocircuitum – % | Pertusa Sine Onere – kW | Pertusa Sub Onere – kW | Currentia Sine Onere – % |
| 6300 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 10 | 36 | 0.8 |
| 8000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 12 | 45 | 0.8 |
| 10000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 14 | 53 | 0.74 |
| 12500 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 17 | 63 | 0.74 |
| 16000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 20 | 77 | 0.69 |
| 20000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 24 | 93 | 0.69 |
| 25000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 28 | 110 | 0.64 |
| 31500 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 34 | 133 | 0.64 |
| 40000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 40 | 156 | 0.58 |
| 63000 | 110, 121, 151 | 6.3, 6.6, 10.5, 11 | YNd11 | 10.5 | 57 | 230 | 0.52 |
| Potentia Nominalis - kVA | Tensio Alta – kV | Tensio Baja – V | Signum connexionis | Impedantia Circuitus Brevis - % | Pertusa Sine Onere – kW | Pertusa Sub Onere – kW | Currentia Sine Onere – % |
| 31500 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 30 | 138 | 0.5 |
| 40000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 36 | 165 | 0.48 |
| 50000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 43 | 180 | 0.48 |
| 63000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 50 | 220 | 0.44 |
| 90000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 64 | 275 | 0.35 |
| 120000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 80 | 369 | 0.35 |
| 150000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 93 | 450 | 0.31 |
| 180000 | 220, 230 | 6.3, 6.6, 10.5, 11, 20, 34.5, 66, 69 | Yd11 | 12‑14 | 105 | 530 | 0.31 |

| Typus Producti | Oleum Transformer immersum |
| Capacitas aestimata | 31500–180000kVA |
| Classe Tensionis | 110kV / 220kV |
| Frequentia censita | 50Hz/60Hz |
| Multis temporibus | Tres fases – secundum configurationem producti |
| Modus refrigerationis | ONAN / ONAF / OFAF, secundum confirmationem generis producti |
| Modus installationis | Instalatio extra aedificium vel intra aedificium |
| Lorem signa | IEC 60076 / GB 1094 |

Tractatio specialis pro mercibus Over‑Out‑of‑Gauge (OOG). Nos regimus totum processum pro transformatoribus gravibus, a confectione custodiarum ad usum specialem et impachetationem sub vacuo usque ad navigationem per rastros planos, per disgregationem, vel per Ro‑Ro.
Expert handling of complex export/import documentation, HS codes, and destination country regulations. We ensure smooth customs clearance to avoid costly delays.
24/7 GPS tracking and milestone updates. Comprehensive cargo insurance covering all risks from origin warehouse to destination site.
Prioritized air freight and expedited sea options for critical breakdowns. We minimize downtime by getting your replacement transformer or parts there faster.
Nos analysamus dimensiones, pondus, et viam ut optime planum transportis designemus.
Impachetatio maritima
Executio transportis maritimi/aerii/terrestris cum strictis protocollis tractationis.
Typus: 3-phase oil immersed distribution transformer
Rated Power: 6300 kVA–180000 kVA
Frequency: 50 Hz / 60 Hz
Normae: IEC 60076 / GB 1094
Customize from Our Standard Product Line
If you spot a near-match in our catalog, we can quickly modify our standard transformers for your application. Adjustments cover capacity, voltage class, cooling type and installation structure.
Build per Your Technical Documents
Send us your specifications or drawings. Our engineering team reviews the design, validates all key parameters with you, and manufactures strictly in accordance with international standards.
Full Custom Design from Concept to Completion
Without formal detailed specs? Share your ideas and functional requirements. We partner with you to develop fully customized transformer solutions, from electrical design and structural layout through to insulation system.